Three-phase transformers auto refrigerated
| KVA |
Average noise level (dB) |
Average noise level (dB) |
| Open |
Encapsulated |
| 0-9 |
40 |
45 |
| 10-50 |
45 |
50 |
| 51-150 |
50 |
55 |
| 151-300 |
55 |
57 |
| 301-500 |
60 |
59 |
| 501-700 |
62 |
61 |
| 701-1 000 |
64 |
63 |
| 1 001-1 500 |
65 |
64 |
| 1 501-2 000 |
66 |
65 |
| 2 001-3 000 |
68 |
66 |
| 3 001-4 000 |
70 |
68 |
| 4 001-5 000 |
71 |
69 |
| 5 001-6 000 |
72 |
70 |
| 6 001-7 500 |
75 |
71 |
| 7 501-10 000 |
79 |
72 |
Open three-phase transformers refrigerated forced air
| KVA |
Average noise level (dB) |
| 0-1167 |
67 |
| 1 168-1 667 |
68 |
| 1 668-2 000 |
69 |
| 2 001-3 333 |
71 |
| 3 334-5 000 |
73 |
| 5 001-6 667 |
73 |
| 6 668- 8 333 |
75 |
| 8 334-10 000 |
78 |
Single-phase transformers self- refrigerated
| KVA |
Average noise level (dB) |
Average noise level (dB) |
| Open |
Encapsulated |
| 0-50 |
50 |
50 |
| 51-167 |
55 |
55 |
| 168-333 |
60 |
60 |
| 500 |
64 |
63 |
| 833 |
65 |
64 |
| 1 256 |
68 |
66 |
| 1 667 |
70 |
68 |
| 2 500 |
71 |
70 |
| 3 333 |
72 |
71 |
| 5 000 |
73 |
72 |
| 10 000 |
79 |
72 |
Open single-phase transformers refrigerated forced air.
| KVA |
Average noise level (dB) |
| 0-50 |
67 |
| 51-167 |
67 |
| 168-333 |
67 |
| 500 |
67 |
| 833 |
68 |
| 1 256 |
70 |
| 1 667 |
71 |
| 2 500 |
72 |
| 3 333 |
74 |
| 5 000 |
76 |
| 10 000 |
78 |
The data included in the tables are based on the Colombian technical standard NTC 5978.